Insulating pieces PS 5 bar, GT5 (ST-GT-F-F)
for separation of electrical currents if possibly appears between gas supply line and gas pipe for interior Installation (only for mounting inside the building), for gas accordance with DVGW code of practice G 260
PS 5 = PS max. 5 bar, TS -20°C to +60°C,
version DIN 3389, (HTB +650°C – 30 min.)
Certifications:
– Pressure Equipment Directive 2014/68/EU ( > Rp 1/R1)
– DVGW-G
Technical specifications:
| Connection/Flange | Pressure | Installation length | tested to | Typ | Weight | Art.-No. | Stock |
|---|---|---|---|---|---|---|---|
| DN 65 | 5 bar | 170 mm | 2 kV | ST-GT-F-F 65 | 8,90 kg | 20018065 | true |
| DN 80 | 5 bar | 180 mm | 2 kV | ST-GT-F-F 80 | 11,30 kg | 20019080 | true |
| DN 100 | 5 bar | 190 mm | 2 kV | ST-GT-F-F 100 | 13,90 kg | 20020100 | true |
| DN 125 | 5 bar | 195 mm | 2 kV | ST-GT-F-F 125 | 17,70 kg | 20023125 | |
| DN 150 | 5 bar | 210 mm | 2 kV | ST-GT-F-F 150 | 23,60 kg | 20021150 | |
| DN 200 | 5 bar | 230 mm | 2 kV | ST-GT-F-F 200 | 34,00 kg | 20022200 |